TAB: General System frequency 50Hz Accept wide input frequency range (45-65 Hz) checked Ground relay checked AC low switch mains off 180 V AC low switch mains on 187 V AC high switch mains on 265 V AC high switch mains off 270 V UPS function checked Dynamic current limiter unchecked Shore current 50.0 A Overruled by remote checked TAB: Inverter PowerAssist checked Inverter output voltage 230 V Assist current boost factor 2.0 Inverter DC shut-down voltage 18.60 V Inverter DC restart voltage 21.80 V Low DC alarm level 21.80 V enable AES unchecked TAB: Charger Enable charger checked Weak AC input unchecked Stop after 10 Hr bulk checked Storage mode checked Use equalization (tubular plate traction battery curve) unchecked Charge curve Adaptive + BatterySafe Absorption voltage 28.80 V Float voltage 27.60 V Charge current 52 A Repeated absorption time 1.00 Hr Repeated absorption interval 7.00 Days Maximum absorption time 8 Hr TAB: Battery monitor State of charge when Bulk finished 85.0 % Battery capacity 200 Ah TAB: Virtual switch TAB: Usage Invert virtual switch usage checked Virtual switch usage drive multifunctional (aux.) relay: VS on=open; VS off=close TAB: A: Set VS ON "High power limit" VS on delay -1 seconds "Low DC level" VS on delay -1 seconds "High DC level" VS on delay -1 seconds "Not charging" VS on delay -1 seconds "Fan on" VS on delay -1 seconds set VS on when bulk protection is activated unchecked set VS on when general system failure occurs unchecked "Temperature pre-alarm" VS on delay 1 seconds "Low-battery pre-alarm" VS on delay 1 seconds "Overload pre-alarm" VS on delay 1 seconds "Udc ripple pre-alarm" VS on delay 1 seconds TAB: B: Set VS OFF "Low power limit" VS off delay -1 seconds "Low DC level" VS off delay -1 seconds "High DC level" VS off delay -1 seconds "Charging" VS off delay -1 seconds "Fan off" VS off delay -1 seconds "Bulk finished" VS off delay -1 minutes "No VS on" VS off delay 0 minutes "No AC input" VS off delay -1 seconds "Temperature pre-alarm" VS off delay -1 seconds "Low-battery pre-alarm" VS off delay -1 seconds "Overload pre-alarm" VS off delay -1 seconds "Udc ripple pre-alarm" VS off delay -1 seconds TAB: VS options Minimum VS on time 0 minutes Change inverter period time when virtual switch is on unchecked Change inverter period time on Udc unchecked